rated insulation voltage (ui) | 500 v | ||
Current consumption | 28 ma, from module bus, supply modules | ||
10.2.7 inscriptions | meets the product standard's requirements. | ||
10.2.2 corrosion resistance | meets the product standard's requirements. | ||
burst impulse | according to iec/en 61000-4-4 | ||
10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
suitable as | segment module | ||
Degree of protection | ip20 | ||
10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
Protocol | other bus systems | ||
10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
power loss | normally 1.3 w | ||
suitable for | base modules with c-connection: 4-wire base modules without c-connection: 2-/3-wire |
||
equipment heat dissipation, current-dependent pvid | 0 w | ||
supply voltage at ac, 60 hz - min | 0 vac | ||
potential isolation | through optocoupler: yes | ||
product category | xn slice module | ||
voltage type | dc | ||
10.3 degree of protection of assemblies | meets the product standard's requirements. | ||
10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
electric connection type | screw-/spring clamp connection | ||
voltage dips | according to en 61131-2 (voltage fluctuations/voltage dips) | ||
10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
supply voltage at ac, 60 hz - max | 0 vac | ||
10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
Features | fieldbus connection over separate bus coupler possible | ||
ambient operating temperature - max | 55 °c | ||
explosion safety category for gas | none | ||
system accessory | yes | ||
Vibration resistance | according to iec/en 60068-2-6 | ||
surge rating | according to iec/en 61000-4-5 level 4 | ||
10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
mounting method | rail mounting possible | ||
10.4 clearances and creepage distances | meets the product standard's requirements. | ||
10.11 short-circuit rating | is the panel builder's responsibility. | ||
radiated rfi | iec/en 61100-4-6 | ||
Product weight | .025 kg | ||
product height | 74.1 mm | ||
ean | 7640130121027 | ||
functions | bus diagnosis possible | ||
10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. |
Shock resistance | mechanical, according to iec/en 60068-2-27 continuous according to iec/en 60068-2-29 |
||
Environmental conditions | harmful gasses - h2s: 1 ppm (relative humidity < 75%, no condensation) harmful gasses - so2: 10 ppm (relative humidity < 75%, no condensation) |
||
10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
Type | xi/on power supply module | ||
supply current | 10 a, iei, maximum operating current, supply modules | ||
ambient storage temperature - max | 85 °c | ||
supply voltage at ac, 50 hz - min | 0 vac | ||
relative humidity | 5 - 95 % (indoor, level rh-2, non-condensing for storage at 45°c) | ||
number of hw-interfaces (other) | 1 | ||
electromagnetic fields | according to iec en 61100-4-2 | ||
10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
air discharge | according to en 61000-4-2 | ||
heat dissipation capacity pdiss | 0 w | ||
Residual ripple | < 5 % (according to en 61131-2) | ||
field voltage | 24 v dc (ul) | ||
drop and topple | according to iec 60068-2-31, free fall according to iec 60068-2-32 | ||
safety performance level (en iso 13849-1) | none | ||
heat dissipation per pole, current-dependent pvid | 0 w | ||
10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
used with | xn-p3t-sbb xn-p4s-sbbc xn-p3s-sbb xn-p4t-sbbc |
||
supply voltage at dc - max | 30 vdc | ||
10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
ambient operating temperature - min | 0 °c | ||
static heat dissipation, non-current-dependent pvs | 1.3 w | ||
emitted interference | 230 - 1000 mhz (radiated, high frequency, according to en 55016-2-3) 30 - 230 mhz (radiated, high frequency, according to en 55016-2-3) |
||
supply voltage at dc - min | 18 vdc | ||
number of bytes | 4 diagnostic bytes | ||
10.8 connections for external conductors | is the panel builder's responsibility. | ||
fitted with: | potential separation | ||
ambient storage temperature - min | -25 °c | ||
10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
10.12 electromagnetic compatibility | is the panel builder's responsibility. | ||
admissible range | 18 - 30 v dc, supply module | ||
rated operational current for specified heat dissipation (in) | 0 a | ||
certifications | ul recognized ul report applies to both us and canada csa class no.: 2252-01, 2252-81 ul 508 iec/en 6113-2 ul category control no.: nraq, nraq7 iec/en 61000-6-2 ce csa-c22.2 no. 142 iec/en 61000-6-4 iec/en 61131-2 culus ul file no.: e205091 certified by ul for use in canada |
||
product width | 12.6 mm | ||
product length/depth | 55.4 mm | ||
explosion safety category for dust | none | ||
sil (iec 61508) | none | ||
supply voltage at ac, 50 hz - max | 0 vac |