Material housing | PA-reinforced PC | ||
Sensor type | +/-10 V +/-20 mA +/-5 V 0 - 10 V 0 - 20 mA 1-5 V 4 - 20 mA | ||
Data format | 15 bits + prefix Scalable to 15 bits | ||
Ambient temperature | -5 °C ... 50 °C | ||
Storage temperature | -20 °C ... 70 °C | ||
Isolation channel - channel | no | ||
Nominal operating voltage DC | 24 V | ||
Basic error limit at 25 °C | ±0.2% | ||
Intern power consumption nominal operating voltage | Typ. 50 mA | ||
Fuse protection (short circuit) | Internal electronic fuse | ||
Internal cycle time | 500 µs | ||
Parameterisation | Data format Forcing per channel Limit monitoring per channel Measured value smoothing Sensor supply active Signal range per channel Behaviour after short circuit Behaviour after input overload Wire break monitoring per channel | ||
Number of inputs | 4 |
Note on materials | RoHS-compliant | ||
Max. cable length | 30 m Shielded | ||
Product weight | 46 g | ||
Degree of protection | Dependent on the manifold block | ||
Corrosion resistance class CRC | 1 - Low corrosion stress (when installed) | ||
Isolation channel - internal bus | Yes, without using the internal sensor supply | ||
Nominal DC operating voltage, load voltage | 24 V +/-2% | ||
Operating error limit related to the ambient temperature range | ±0.3% | ||
Operational voltage range DC | 18 V ... 30 V | ||
Repetition accuracy | 0.1% at 25ºC | ||
LED display | 1 Group diagnostics 4 channel diagnostics | ||
Diagnosis | Wire break per channel Limit value violation per channel Parameterisation error Overflow/underflow Input overload Short circuit of sensor supply | ||
Dimensions (W x L x H) | (incl. interlinking block and connection technology) 50 x 107 x 50 mm |